OPERATING YOUR 25176B1. Inspect the 25176B thoroughly to insure that it is in good operating condition.2. Make sure all connections are correct and ti
SELF PURGING YOUR 25176BPROCEDURE FOR PURGING REMAINING REFRIGERANT FROM THE 25176B1. Close the ports of the system being serviced that are connected
See page 10 of this manual for more information.1. To start you must have a minimum of 5 lbs.of liquid refrigerant in the tank.2. Put RECOVER/PURGE k
OPTIONAL RECOVERY/TANK PRE OR SUBCOOLING FOR FIXED HOSE SET-UPm A scale must be used to avoidover filling the storage tank.NORMAL RECOVERY:Tank Vapor
REFRIGERANT FLOW DIAGRAMNOTE: A filter must always be used. Failure to use a filter will invalidate your warranty.The use of a filter will greatly red
1625176B PARTS DIAGRAM25176B PARTS LISTREPLACEMENT KITS & ACCESSORIES*OPTIONAL COMPONENTS FOR 80% CAPACITY TANK SENSING KITPART# DESCRIPTIONKT3302
25176B WIRING DIAGRAMWIRENUTSTART SWITCHPRESSURE SWITCHH. P. LAMPFOR UPGRADE3 PIN CONNECTORSIDE OF MANIFOLDBRNGRNPOWERSWITCHFANMOTORBRNMOTOR1/2 HPREDT
INSTALLATION OF OPTIONAL 80% TANKCAPACITY SENSING COMPONENTS (KIT: KT-5001)18Note: ROBINAIR also offers the model, 25176B-KT,with the 80% Capacity Shu
TROUBLESHOOTING YOUR 25176BSAFETY FIRSTRead and understand all safety information contained inthis manual before servicing the unit.CONNECT UNIT TO220
FULL ONE YEAR WARRANTYMFG#Robinair products are warranted to be free from defects in workmanship and materials for a period of oneyear from date of pu
TABLE OF CONTENTSIMPORTANT SAFETY INFORMATION 4OPERATING GUIDELINES 5-6CARE AND MAINTENANCE OF YOUR 25176B 6ADDITIONAL RECOVERY TANK INFORMATION 7PURG
THE UNITED STATES ENVIRONMENTAL PROTECTION AGENCY (EPA) REFRIGERANT RECOVERY AND RECYCLING DEVICE ACQUISITION CERTIFICATION FORMEPA regulations have r
INSTRUCTIONS EPA REGIONAL OFFICES22Part 1. Please provide the name, address and telephonenumber of the establishment where the refrigerant recov-ery o
PN/ 100439 Rev'%RVFK$XWRPRWLYH6HUYLFH6ROXWLRQV//&Toll Free; 1-800-327-5060Fax: www.RobinairHVAC.com100439_RevC.qxd 9/2
m IMPORTANT SAFETY INFORMATION mSAFETY COMES FIRST! Read all safety, operatingguidelines and instructions before operating your25176B.1. CAUTION: ONL
m Before operating the 25176B recovery unit, read the following m1. 25176B IS APPROVED FOR USE WITH THE FOLLOWING CATEGORY III, IV and V REFRIGERANT
NOTE: If there is no liquid in the recovery tank, thenthe cooling method will not work. In this case, use anempty tank that has been fully evacuated t
m Warning: Also read the information pertain-ing to recovery tanks, previously listed underSafety Information and Operating Guidelines.1. CAUTION: NE
81. Allow the tank to sit undisturbed for 24 hours. This allows the air to rise to the top.2. Connect a manifold to the tank and read the amount of pr
HELPFUL HINTS FORREFRIGERANT RECOVERYPLANNING AHEADKnowing the quantity of refrigerant is important for plan-ning storage requirements, as well as pla
HELPFUL HINTS FORREFRIGERANT RECOVERY - cont.This is probably never noticed in charging, because thepressure opens the grommet, but during recovery (o